Product List

Add.: Tellhow Industrial Area, High-tech Industrial Area, Guanlan Town, Baoan District, Shenzhen City, Guangdong Province, China
Mobile Phone: +86-13631533273

12KV-24KV Circuit Breaker Truck

Circuit Breaker Truck for 12KV~24KV Circuit Breaker

Features and Applications
The 12-24kV circuit breaker truck is mainly used for mounting components such as circuit breakers, transformers, etc by withdrawable switchgears. It allows the components to run in and run out, facilitating their connection with the busbar. Our circuit breaker truck is interchangeable with ABB-VD4, Schneider-EV12S, HVX and Tellhow-TZN etc.

Lock Plate

Note:Circuit breaker truck has five Locking Plates for selection, the standard Locking Plates is 8XS.141.012.2 that match with ABB-VD4, Schneider-EV12S, HVX, Tellhow-TZN etc.

Grounding Way of Circuit Breaker Truck
1. Earthing bar mounting dimensions
2. Ground contacts mounting dimensions
Dimensions of Circuit Breaker Truck
1. Manual Circuit Breaker Truck for 12KV Circuit Breaker
Installation dimension
Type A B C D E F
DPC-4-650 500 450 410 385Installation hole 13x30 502 532
DPC-4A-650 500 450 410 385Installation hole 13x30 502 532
DPC-4-800 650 600 560 520 652 682
DPC-4A-800 650 600 560 520 652 682
DPC-4-840 690 640 600 560 692 722
DPC-4A-840 690 640 600 560 692 722
DPC-4-900 750 700 660 620 752 782
DPC-4A-900 750 700 660 620 752 782
DPC-4-1000 850 800 760 720 852 882
DPC-4A-1000 850 800 960 720 852 882
DPC-4-1200 1050 1000 760 920 1052 1082
DPC-4A-1200 1050 1000 960 920 1052 1082
2. Manual Circuit Breaker Truck for 24KV Circuit Breaker
  • Manual Circuit Breaker Truck for 24KV Circuit Breaker
    DPC-4A-800-24-X300
  • Manual Circuit Breaker Truck for 24KV Circuit Breaker
    DPC-4A-1000-24-X300
Unit: mm
Model A B C D E F G
DPC-4A-1000/24 850 800 760 710 645 852 882
DPC-4A-1100/24 950 900 860 810 745 952 982
DPC-4A-1200/24 1050 1000 960 910 845 1052 1082

Special Circuit Breaker Trucks: Electric Circuit Breaker Truck

Introduction:
By increasing electrical operating functions and control modules, the circuit breaker truck enables the medium voltage switchgear to be intelligent,programmable, and remote controllable. The electrical mechanism of this circuit breaker truck can be mounted horizontally and directly on the original withdrawable circuit breaker truck without changing dimensions and interlock functions of the manual chassis. It is easy to switch between manual and electrical operation.

Advantages:
There are multiple control modules available for selection to meet different customer needs.
Manual and electrical operations can be easily and automatically switched between each other by remote control.
Preventive voice reminding function: to prevent misuse in test and operation.
Micro switches are available for testing and working positions.

Electric Circuit Breaker Truck Dimensions

1. 12kV Electric Circuit Breaker Trucks
Installation dimension
Type A B C D E F
DPC-4-650 500 450 410 385Installation hole 13x30 502 532
DPC-4A-650 500 450 410 385Installation hole 13x30 502 532
DPC-4-800 650 600 560 520 652 682
DPC-4A-800 650 600 560 520 652 682
DPC-4-840 690 640 600 560 692 722
DPC-4A-840 690 640 600 560 692 722
DPC-4-900 750 700 660 620 752 782
DPC-4A-900 750 700 660 620 752 782
DPC-4-1000 850 800 760 720 852 882
DPC-4A-1000 850 800 960 720 852 882
DPC-4-1200 1050 1000 760 920 1052 1082
DPC-4A-1200 1050 1000 960 920 1052 1082
2. 24kV Electric Circuit Breaker Trucks
  • 24kV electric circuit breaker trucks
    DPC-4A-800-24-X300
  • 24kV electric circuit breaker trucks
    DPC-4A-1000-24-X300

Supporting Control Module
The electric circuit breaker truck provides a driving solution, but to control and protect the electric circuit breaker truck is only possible with appropriate control device. To meet customers’ requirements, we developed four control modules with different functions.

1. DD-2B+ Control Module

1.1 The control module has the following features:
a. adapt to basic control over the run-in and run-out of circuit breaker truck, as well as interlock with circuit breaker and earthing switch.
b. with motor over-current protection, and the over current can be adjusted.
c. overcurrent return function:in the case of overcurrent, the motor can return to the test position, or return by half circle.
d. overtime protection: if no truck-in-place signal is detected by the control module within the set time, the running will automatically stop.
e. the control module is installed in the low voltage control room of the medium voltage switchgear.

2. DD-3 Control Module

2.1 Overview
DD-3 series electric circuit breaker trucks control module can achieve the control and protection of the chassis, with local and remote two modes of operation. In the case that the drive motor of the electric circuit breaker truck is blocked and protection is needed (such as the installation is not in place or mechanism gets stuck), the control module will immediately brake the motor and reverse it to relieve the seized state.

2.3 Advantages (compared with DD-2B+ type):
a. with removable terminals for easy installation and maintenance.
b. combined use of panel buttons enables emergency braking function to avoid accidents in a timely manner.
c. remote / local operation of the internal latch simplifies the external circuit design and assembly.
d. dimension shrinks; cabinet and panel mounting are both available.
e. with run-in and run-out reset buttons for easy commissioning operations.
f. overcurrent adjustment is taken place by the segmented current settings, which brings more effective protection.
g. public terminal is used and the number of external terminals are reduced from 22 to 18 to facilitate wiring.
h. emergency stop function is added: press the run-in and run-out buttons at the same time can achieve urgent braking.

Parameters

DD-3A DD-3B DD-3C
Voltage AC/DC 110V, 220V AC/DC 110V, 220V AC/DC 110V, 220V
Rated motor power DC110V, 220V , Max. 300W DC110V, 220V , Max. 300W DC110V, 220V ,rated power below 300W
Fault output contact 1NO, 5A, AC250V 5A , AC250V 5A , AC250V or DC30V
Power consumption < 2W < 2W < 5W
Power frequency withstand voltage AC2.5KV/1min AC2.5KV/1min AC2.5KV/1min
Protection class IP50 IP50 IP20
Ambient temperature -25 ℃ to +55℃ -25 ℃ to +55℃ -20 ℃ to +50℃
Dimensions (L×D×H) 125×59× 88mm 165×59×100mm 78×73×125mm
Installation cabinet, DIN35mm rail mounted or fixed cabinet, DIN35mm rail mounted or fixed panel, DIN35mm rail mounted
Outline and Installation Dimension
1. DD-2B+ Control Module
2. DD-3A Control Module
3. DD-3B Control Module
4. DD-3C Control Module

We are a professional power equipment supplier and power transmission expert based in China. To find the best power distribution solutions, just find us!